1 INSTRUMENT HANDBOOK DeviceNet VP51 Digital Proportional Control Valve To download the product EDS file visit www.odva.org
10 Changing MACID or Baud Rate From Normal Operating Mode When the Device is in normal operating mode (i.e. communicating on DeviceNet), the baud r
11 8. EC DECLARATION OF CONFORMITY The DeviceNet VP51 Digital Proportional Valve complies with the EC Pressure Equipment Directive and the generic
2 Table of Contents 1. Introduction 2. Safety 3. Operating Description 4. Dimensional Details 5. Installation • Pneumatic • Electrical •
3 3. OPERATING DESCRIPTION The DeviceNet VP51 is a programmable electronic proportional control valve. The pneumatic section is a diaphragm actua
4 5. INSTALLATION Pneumatic Installation • Supply Pressure: 15psig above maximum output required (200psig max.) • Output Pressur
5 DeviceNet Installation • Download the DeviceNet VP51 EDS file from www.odva.org • Register the EDS file using a DeviceNet configuration tool
6 6. DEVICENET INTERFACE DETAILS I/O Data Name I/O Type (see Note 1) No. Bytes Format Demand Pressure Polled Output 2 12 bit integer (0 to 409
7 Parameter No. Name Format Default Value Class Id Instance Id Attribute Id Byte length 4 Actual Pressure Read only integer, 0-4095 0 = minimum (z
8 Fig. 1 - Speed Setting Effects at default Proportional and Integral Gain024681012TimePressure, bar Fig. 2 - Proportional Gain Effects at default
9 7. LOCAL USER INTERFACE DETAILS The DeviceNet VP51 includes an integral keypad and LCD display. During normal operation, this will display the c